ANALISA HARMONISA PEMBANGKIT LISTRIK TENAGA SURYA (PLTS) OFF - GRID 290 Wp DENGAN KOMBINASI BEBAN LINIER DAN NON LINIER DI GEDUNG FAKULTAS TEKNIK UKI - JAKARTA MENGGUNAKAN MATLAB SIMULINK

  • Elisabeth Faustina Ene Openg Universitas Kristen Indonesia
  • Bambang Widodo Universitas Kristen Indonesia
  • Robinson Purba Universitas Kristen Indonesia
Keywords: Off-Grid Solar Photovoltaic System, Harmonics, Linear Loads, Non-Linear Loads, Passive Single Tuned LC Filter, MATLAB Simulink.

Abstract

 This paper presents the results of research on a 290 Wp (Watt-peak) Off-Grid Solar Power Plant (PLTS) at the Faculty of Engineering Building, Universitas Kristen Indonesia - Jakarta, aiming to investigate current harmonics on the load side and reduce the Total Harmonic Distortion (THDi) value using a single-tuned LC passive filter. Based on the measured current per order, calculations were conducted, revealing that the THDi on the load side (LED) amounted to 16,42%. The dominant harmonic currents were the 3rd order with a THDi of 5,7% and the 10th order with a THDi of 15,3%. According to the simulation results using MATLAB Simulink, the single-tuned LC passive filter was capable of reducing the THDi level on the LED from 16,42% to 1,81%.

Published
2024-03-21
How to Cite
Openg, E. F. E., Widodo, B., & Purba, R. (2024). ANALISA HARMONISA PEMBANGKIT LISTRIK TENAGA SURYA (PLTS) OFF - GRID 290 Wp DENGAN KOMBINASI BEBAN LINIER DAN NON LINIER DI GEDUNG FAKULTAS TEKNIK UKI - JAKARTA MENGGUNAKAN MATLAB SIMULINK. Lektrokom : Jurnal Ilmiah Teknik Elektro, 7(1), 1-13. https://doi.org/10.33541/lektrokom.v7i1.5658

Most read articles by the same author(s)

1 2 3 4 > >>